FR-XOL, CU / MGT / XLPE / OS / LSZH, Single pair

FR-XOL, CU / MGT / XLPE / OS / LSZH, Single pair, Mica taped, XLPE insulated, Overall aluminium foil screened, LSZH sheathed, 300/500V cable - compliant with BS EN50288-7

Construction

Conductor: Plain annealed copper, Class 2 stranded circular
Fire Barrier: Mica tape (MGT)
Insulation: Cross-linked Polyethylene (XLPE) compound
Insulation colour: Black, White or Others
Lay up: Pair – Cores twisted to pair
Wrap film: Polyester binder tape
Overall screen: Aluminium/Polyester tape, with a tinned copper drain wire 0.5mm² (7/0.3mm²) (OS)
Outer sheath: Low-Smoke Zero-Halogen (LSZH) compound with anti-termite characteristics and UV resistant
Outer sheath colour: Orange or others

Electrical Characteristics

Operating voltage U0 / U: 300/500V
Operating temperature: -15°C to +90°C
Final short circuit temperature: 250°C
Test voltage: 2kV for 1 minute

Reference Standards

Design specification: BS EN50288-7
Conductor: IEC60228, BS EN60228
Fire resistance: BS6387 (C,W,Z), SS299 (C,W,Z), IEC60331
Flame retardancy: IEC60332-3-22, BS EN60332-3-22
Low-Smoke Zero-Halogen: IEC61034-2, BS EN61034-2, IEC60754-1, IEC60754-2, BS EN60754-1, BS EN60754-2

Installation Reference

Minimum bending radius (mm): 8 x cable overall diameter
Maximum pulling tension: 50N/mm²